How should I wire the X1 and X2 terminals on my XBus controller?

The X1 and X2 terminals should be connected to the corresponding terminals on the thermostat. It is recommended to balance the number of connections to each of the four terminals on the controller. If you have an older controller with only three terminals balance the number of wires connecting to the two X1 terminals.

I had a power outage and now I cannot connect to some of my XBus/Strongmesh thermostats in the Command Center software. How do I get them back online?

In the event of a power outage or power surge, the thermostats may reset and go back to address 1. Check the thermostat addresses by holding the mode and fan buttons simultaneously for twelve seconds, this will show the address of the thermostat. Multiple thermostats with the same address will cause the controller not be able to communicate with them. In this case, set the thermostats back to the correct addresses. If you do not find a solution to the issue in this FAQ section, contact support.

Is there a way to force the second stage to come on?

If your equipment is 2-stage, first make sure your DIP switches are set correctly to allow second stage operation. In order to bring on second stage faster than the efficient fuzzy-logic algorithm (about 15-20min after first stage, if needed):